NA2XY 0.6/1 kV Single Core Power Cable with Aluminium Conductor, XLPE Insulation and PVC Jacket

NA2XY
Conductor
Stranded aluminium, compacted (Class 2)
Insulation
Cross-linked polyethylene (XLPE)
Outer sheath
PVC
Rated voltage
0.6/1 kV (Um = 1.2 kV)
Product Overview

Specifications

Feature Value
Conductor Stranded aluminium, compacted (Class 2)
Insulation Cross-linked polyethylene (XLPE)
Outer sheath PVC
Rated voltage 0.6/1 kV (Um = 1.2 kV)
Max. continuous operating temperature 90 °C
Max. short circuit temperature 250 °C
Standard IEC 60502-1
  • Indoor or outdoor installations where there is no mechanical damage risk
  • Power cable with extruded insulation for rated voltages of 1 kV (Um = 1.2 kV)
Damar Sayısı × Kesit
No. × Nominal Area (mm²)
Faz İletkeni Min. Tel Sayısı
Min. No. of Wires in Phase
Nominal İzole Kalınlığı
Nominal Insulation Thickness (mm)
Nominal Dış Kılıf Kalınlığı
Nominal Outer Sheath Thickness (mm)
Dış Çap (Yaklaşık)
Overall Diameter (approx.) (mm)
Birim Ağırlık (Yaklaşık)
Unit Weight (approx.) (kg/km)
20 °C'de DC Direnç
DC Resistance at 20 °C (Ω/km)
Akım Taşıma Kapasitesi – Havada (A)
Current Carrying Capacity – In Air (A)
Akım Taşıma Kapasitesi – Yer Altında (A)
Current Carrying Capacity – Under Ground (A)
Düz
Flat
Üçgen
Trefoil
Düz
Flat
Üçgen
Trefoil
1x2560,901,410,31651,200136106177114
1x3560,901,411,32000,868166130212136
1x5061,001,412,72450,641205161252162
1x70121,101,414,83300,443260204310199
1x95151,101,516,54200,32321252372238
1x120151,201,518,05100,253376295425272
1x150151,401,620,26300,206431339476305
1x185301,601,622,57800,164501395541347
1x240301,701,725,19750,125600472631404
1x300301,801,827,611500,100696547716457
1x400532,001,931,415450,0778821643825525
1x500532,001,935,021000,0605971754952601
1x630532,402,240,025500,046911518821102687